flex7 Applications – Setting/Recalling Scenes

Wiring Connection

DESCRIPTION | PART NO. |
---|---|
1 X Starter Distribution Box | FSU08 |
1 x Control Pack | FNC4000X/AB |
1 x Scene Set Plate | FSS04/K/W/WP |
1 X Switch Drop Lead | FSL10/BL |
4 X DALI Luminaire Lead | FL5100LSHF5/BD |
2 X DALI Maintained Emergency Luminaire Lead | FL6100LSHF5/RD |
Control Device Properties
Scene Set Plate is a push button device.
Scene Set Plate operates at Protected Extra Low Voltage (PELV) – nominally 12V.
Operation
Luminaires are all turned on at a particular light level by pushing one of the buttons marked 1-4 on the Scene Set Plate.
By default these are factory set at 100%, 75%, 50%, 25% but each can be reprogrammed at any time to any desired value.
Pushing the master button at the top right hand corner of the Scene Set Plate will turn all luminaires off.
All luminaires must have DALI drivers / control gear.
Installation
- Install the Distribution Box using the fixing kit provided.
- Terminate the fixed wiring into the Distribution Box terminals – see schematic above.
- Fit the Scene Set Plate – it mounts onto a standard 25mm deep single box with 60.3mm centres.
- Plug the Control Pack into any outlet on the Distribution Box.
- Plug one end of the Switch Drop Lead into the Control Pack.
- Plug one end of the Switch Drop Lead into the Scene Set Plate.
- Plug the luminaires into any outlet on the Distribution Box.
Tips and Tricks
Using the numbered buttons on the Scene Set Plate it’s possible to set a PIN so that the preset light levels cannot be changed inadvertently.
The up/down arrows on the Scene Set Plate allow a scene’s light level to be temporarily raised or lowered. The next time that numbered button is pressed the preset scene will be recalled, not the temporary one.
For correct operation, ensure the LED Mode indicator (bottom right of Scene Plate) is NOT lit. Use the Mode button (bottom right of Scene Plate) to turn Mode LED off.