flex7 Applications – Presence Control With Daylight Linking To All Luminaires

Schematic of a room with 6 luminaires, all wired up with presence control and daylight linking enabled.

Wiring Connection

 

DESCRIPTION PART NO.
1 X Starter Distribution Box FSU08
1 x Control Pack FNC4000X/AB
1 x Primary PIR Sensor Head FNH400
1 x Sensor Lead FSL05
4 X DALI Luminaire Lead FL5100LSHF5/BD
2 X DALI Maintained Emergency Luminaire Lead FL6100LSHF5/RD
1 X Setup Remote Control FRC/SET

Control Device Properties

Sensor Head is a passive infrared (PIR) device that detects movement within a defined area – 9m x 7m when mounted at a height of 2.5m.

PIR Sensor Head also includes an integral light sensor that can measure variations in the available ambient light.

PIR Sensor Head operate at Protected Extra Low Voltage (PELV) – nominally 12V

Operation

Luminaires are all automatically turned on when movement is detected by the PIR Sensor Head.

The integral light sensor measures the available ambient light and maintains the area’s set target level by decreasing or increasing the light output of the luminaires.

Once the area is vacated and the PIR Sensor Head has completed its timeout sequence the luminaires will automatically switch off.

Luminaires adjacent to the window must have DALI drivers/control gear

Installation

  1. Install the Distribution Box using the fixing kit provided.
  2. Terminate the fixed wiring into the Distribution Box terminals – see schematic above.
  3. Fit PIR Sensor Head – requires a 32mm hole.
  4. Plug the Control Pack into any outlet on the Distribution Box.
  5. Plug one end of the Sensor Lead into the Control Pack.
  6. Plug one end of the Sensor Lead into the PIR Sensor Head.
  7. Plug the luminaires into any outlet on the Distribution Box.
  8. Using a Setup Remote Control (FRC/SET) enable presence.
  9. Using a Setup Remote Control (FRC/SET) set the desired target light level.

Tips and Tricks

The green power LED on the top of the Control Pack will blink steadily to indicate one or more PIR Sensor Heads are connected to it.

A solid green LED signifies the Control Pack is powered but has no connected PIRs.

If a target light level is not set, the luminaires will not daylight link and remain at full brightness whilst ever they are on.