flex7 Applications – Presence Control – 2 x Sensor Heads

Presence control wired using flex7 lighting connection and control system.

Wiring Connection

 

 

 

DESCRIPTION PART NO.
1 X Starter Distribution Box FSU08
1 x Control Pack FNC4000X/AB
1 x Primary PIR Sensor Head FNH400
1 x Auxiliary PIR Sensor Head c/w Y Connector FNH/AUX
2 x Sensor Lead FSL05
4 X Standard (on/off) Luminaire Lead F3100LSHF5/W
2 X Maintained Emergency Luminaire Lead FL4100LSHF5/R
1 X Setup Remote Control FRC/SET

Control Device Properties

Sensor Heads are passive infrared (PIR) devices that detect movement within a defined area – 9m x 7m when mounted at a height of 2.5m

PIR Sensor Heads also include an integral light sensor that measure variations in the available ambient light.

PIR Sensor Heads operate at Protected Extra Low Voltage (PELV) – nominally 12V

Operation

Luminaires are all automatically turned on when movement is detected by either PIR Sensor Head.

Once the area is vacated and both PIR Sensor Heads have completed their individual timeout sequence the luminaires will automatically switch off.

Installation

  1. Install the Distribution Box using the fixing kit provided.
  2. Terminate the fixed wiring into the Distribution Box terminals – see schematic above.
  3. Fit the PIR Sensor Heads – each requires a 32mm hole.
  4. Plug the Control Pack into any outlet on the Distribution Box.
  5. Plug the Y Connector into the Control Pack.
  6. Plug one end of each Sensor Lead into the Y Connector.
  7. Plug one end of each Sensor Lead into a PIR Sensor Head.
  8. Plug the luminaires into any outlet on the Distribution Box.
  9. Using a Setup Remote Control (FRC/SET) enable presence.

Tips and Tricks

More PIR Sensor Heads can be added to ensure positive detection in larger areas or where occupants are mainly sedentary – desk based.

A maximum of 5 Auxiliary Adaptor Sensor Heads can be added to a Primary Sensor Head – 6 PIR Sensor Heads in total.

Never connect 2 Primary Sensor Heads directly to a single Control Pack – the devices will not be damaged, but they will not operate as intended. Auxiliary Sensor Heads (FNH/AUX) are supplied c/w a Y Connector (FSY/A).

Y Connectors can be plugged into Control Packs, PIR Sensor Heads or, where multiple Y Connectors are required, any combination of the two.