flex7 Applications – Presence Control – 2 x Sensor Heads

Wiring Connection

DESCRIPTION | PART NO. |
---|---|
1 X Starter Distribution Box | FSU08 |
1 x Control Pack | FNC4000X/AB |
1 x Primary PIR Sensor Head | FNH400 |
1 x Auxiliary PIR Sensor Head c/w Y Connector | FNH/AUX |
2 x Sensor Lead | FSL05 |
4 X Standard (on/off) Luminaire Lead | F3100LSHF5/W |
2 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
1 X Setup Remote Control | FRC/SET |
Control Device Properties
Sensor Heads are passive infrared (PIR) devices that detect movement within a defined area – 9m x 7m when mounted at a height of 2.5m
PIR Sensor Heads also include an integral light sensor that measure variations in the available ambient light.
PIR Sensor Heads operate at Protected Extra Low Voltage (PELV) – nominally 12V
Operation
Luminaires are all automatically turned on when movement is detected by either PIR Sensor Head.
Once the area is vacated and both PIR Sensor Heads have completed their individual timeout sequence the luminaires will automatically switch off.
Installation
- Install the Distribution Box using the fixing kit provided.
- Terminate the fixed wiring into the Distribution Box terminals – see schematic above.
- Fit the PIR Sensor Heads – each requires a 32mm hole.
- Plug the Control Pack into any outlet on the Distribution Box.
- Plug the Y Connector into the Control Pack.
- Plug one end of each Sensor Lead into the Y Connector.
- Plug one end of each Sensor Lead into a PIR Sensor Head.
- Plug the luminaires into any outlet on the Distribution Box.
- Using a Setup Remote Control (FRC/SET) enable presence.
Tips and Tricks
More PIR Sensor Heads can be added to ensure positive detection in larger areas or where occupants are mainly sedentary – desk based.
A maximum of 5 Auxiliary Adaptor Sensor Heads can be added to a Primary Sensor Head – 6 PIR Sensor Heads in total.
Never connect 2 Primary Sensor Heads directly to a single Control Pack – the devices will not be damaged, but they will not operate as intended. Auxiliary Sensor Heads (FNH/AUX) are supplied c/w a Y Connector (FSY/A).
Y Connectors can be plugged into Control Packs, PIR Sensor Heads or, where multiple Y Connectors are required, any combination of the two.